FLUKE 6500-2 (Model 6500-2) is a FLUKE supplied by Guangzhou Yunke Electronics Co., Ltd. FLUKE 6500-2 — FLUKE · Yunke Electronics. Request a quotation and datasheet.
Brand: FLUKE | Category: FLUKE
Sales Inquiries: 15626018696 · 78403603@qq.com

| Test | Display Range Accuracy Index Setting is ±(% Reading + digits Number), Applicable at 23°C ±5°C, ≤75% RH when. |
|---|---|
| Electric Test | Test Indication toward L-N, PE, and Measurement Power Supply Voltage and Frequency. |
| Electric Test Display Range | 90 V to 264 V |
| Electric Test Accuracy @ 50 Hz | ±(2% + 3 digits) |
| Electric Test Resolution | 0.1 V |
| Electric Test Input | > 1 MΩ / 2.2 nF |
| Electric Test Maximum Input Power Supply Voltage: | 264 V |
| Grounding Connection Test (Rpe) | Display Range 0 to 19.99 Ω |
| Grounding Connection Test (Rpe) Accuracy (Grounding Test Zero Adjustment Rear) | ±(5% + 4 digits) |
| Grounding Connection Test (Rpe) Resolution | 0.01 Ω |
| Grounding Connection Test (Rpe) Test Current | 200 mA AC -0% +40%,1.99 Ω / 10 A AC ±20%,25 mΩ @ 230 V |
| Grounding Connection Test (Rpe) Voltage | > 4 V AC、< 24 V AC |
| Grounding Connection Test (Rpe) Grounding Test Zero Adjustment | up to minus 1.99 Ω |
| Insulation Test (Riso) | Display Range 0 to 299 MΩ |
| Insulation Test (Riso) Accuracy | ±(5% + 2 digits), 0.1 to 300 MΩ |
| Insulation Test (Riso) Resolution | 0.01 MΩ (0 to 19.99 MΩ) / 0.1 MΩ (20 to 199.9 MΩ) / 1 MΩ (200 to 299 MΩ) |
| Insulation Test (Riso) Test Voltage | 500 V DC -0% + 25% @ 500 kΩ Load, or 250 V dc -0% +25% @ 250 kΩ Load |
| Insulation Test (Riso) Test Current | > 1 mA @ 500 kΩ Load, < 15 mA @ 0 Ω |
| Insulation Test (Riso) Automatic Discharging Time | < 0.5 s,1 μF |
| Insulation Test (Riso) Maximum Load | Operation Height up to 1 μF |
| Contact Current Test | Display Range 0 to 1.99 mA, AC |
| Contact Current Test Accuracy | ±(4% + 2 digits) |
| Contact Current Test Resolution | 0.01 mA |
| Contact Current Test Internal Part Resistance (Via Probe) | 2 kΩ |
| Contact Current Test Measuring Method | Probe * |
| Current Test | Display Range 0 to 19.99 mA, AC |
| Current Test Accuracy | ±(2.5% + 3 digits) |
| Current Test Resolution | 0.01 mA |
| Current Test Test Voltage | 100 V AC ±20% |
| Load / Leakage Test: Load Current | Display Range 0 A to 13 A |
| Load / Leakage Test: Load Current Accuracy | ±(4% + 2 digits) |
| Load / Leakage Test: Load Current Resolution | 0.1 A* |
| Load / Leakage Current Test: Load Power | Display Range 230 V Power Supply 0.0 VA to 3.2 kVA |
| Load / Leakage Current Test: Load Power Accuracy | ±(5% + 3 digits) |
| Load / Leakage Current Test: Load Power Resolution | 1 VA (0 to 999 VA), 0.1 kVA (>1.0 kVA)* |
| Load / Leakage Current Test: Leakage Current | Display Range 0 to 19.99 mA |
| Load / Leakage Current Test: Leakage Current Accuracy | ±(4% + 4 digits) |
| Load / Leakage Current Test: Leakage Current Resolution | 0.01 mA* |
| PELV Test | Accuracy @ 50 Hz ±(2% + 3 digits) |
| PELV Test Overload Protection | 300 V rms |
| PELV Test Alarm Limit | 25 V rms |
| RCD Test: Trip Current | Operation Error ±10% |
| RCD Test: Trip Current Nominal Value | 30 mA |
| RCD Test: Trip Current Accuracy | ±5% |
| RCD Test: Trip Time | Standard 61557 No. 6; Rated Test Current Difference is 0% to +10% |
| RCD Test: Trip Time Operation Error | ±10% |
| RCD Test: Trip Time RCD Type | AC General-purpose 30 mA |
| RCD Test: Trip Time Display Range | 310 ms |
| RCD Test: Trip Time Resolution | 0.1 ms |
| RCD Test: Trip Time Accuracy | 3 ms |
| RCD Test: Trip Time Trip Time Limit Value @100% (30 mA) | 300 ms |
| RCD Test: Trip Time Trip Time Limit Value @500% (150 mA) | 40 ms |
| Operating Temperature | 0 to 40°C |
| Relative Humidity | Non- Condensation <10°C |
| Safety Class | Compliant with EN61010-1 No. three Version |
| Dimensions (Length X Width X Height) | 200 x 275 x 114 mm |
| Weight | 3.13 kg |
| Power Supply | 230 V +10% -15%, 50 Hz ±2 Hz or (only Limit 6500-2: 110V +10% -15%, 50 Hz ±2 Hz) |
| Power Consumption (Test Instrument) | 13 W Typical (Standby) / 60 W Maximum, 25A Grounding Test |
| Storage | Temperature -10 to 60°C |
| Storage | 70°C @ 95% Rh, up to 5 |
| Operating Altitude | 0 to Maximum 2000 m |
| Sealing | IP-40 (Housing), IP-20 (Connection Device) |
| EMC | Compliant with EN61326-1 Standard, Portable Type |
| EMI | 3 V / m |
Some specification lines are quoted from the original manufacturer datasheet. Numbers, units and model codes are preserved verbatim; an English datasheet is available on request.
More tests are implemented daily for Fluke 6500-2 EPS test devices, which are light, small, one-key solutions with re-engineered autotesting features, and are designed to provide a more efficient and effective way to improve the quality of the environment. Q1 -2 Q4 QSystrange solutions, which are simple and simple, and the autotest function is redesigned. The purpose of 6500-2 is to work faster without affecting the results of the tests. One-key solution. just press the button._ This will enable the preset test program to be started. Not only will the test be simplified, but it will also allow for faster and more efficient ways of working.6500-2 is fully automated. Qwerty keyboard with user-defined test programs and easy to fast-load data. Light weight 6500-2 weighing approximately 3 kg, light weight and easy to carry, It's easy to work on the spot. It's a solid, durable portable box (tagged) that not only provides transport protection, but also provides additional storage space to facilitate storage of spare parts and other tools. Small. the portable electrical tester is very compact. The Fluke EPS test is a complete integrated solution with all the features required to test portable appliances. Reference: Fluke
• Testing of installation projects for electrical equipment, servicing of medical equipment, home power production lines and laboratories. —
Q: FLUKE Fluke 6500-2 Portable Safety Tester, what can be done primarily?
A: FLUKE Fluke 6500-2 Portable Seter Tester is a portable Seter product for FLUKE Fluke. . Q XSpT. . Q XPS. X The main functions listed officially include: a special key, which can be completed by a "one key" for each test; a pre-qualified/unqualified limit value, which saves time; a bright, bright backlight screen, which is clear and easy to read. Survey object and process requirements can be provided and confirmed with cloudy assistance
Q: What are the key technical indicators for 6500-2? Q: What are the key technical indicators? Q: Q: Q: Q: Q: Q: Q: Q: Q
A: The list of parameters for this page has been compiled by official information and contains a total of 70 projects covering technical indicators/* electrical power supply through municipal power sources./Environmental indicators/safety indicators..A.A.A..A. For more detailed accuracy and environmental conditions, please refer to the official manual and this page is not open article by article.!
Q: How can the selection and the cargo date be confirmed?!
A: Guangzhou Yunke Electronics Co., Ltd. supplies a full range of FLUKE Fluke products, which can provide selective advice, technical information and post-sale support. Please provide a specific model, quantity and usage profile, which will be confirmed with the assistance of staff
Q: What is the type of portable safety test for FLUKE Fluke 6500-2? What are the scenarios?
A: This product is a portable installation test (FLUKE Fluke/ Portable installation tester). for electrical equipment, service medical equipment, home electrical production lines and laboratories
Q: How can technical support be obtained after purchase?!
A: Products with official instructions and quality assurance services; Guangzhou Yunke Electronics Co., Ltd. provides pre-sale selection and post-sale coordination services, which can be submitted through site contact, supported by staff assistance to connect to the original plant
All model codes, numbers and units are preserved verbatim from the original manufacturer datasheet. An English datasheet is available on request.
For a quotation, lead time or an optional calibration certificate, please contact our engineers.